Engineered air DJ Series Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Raumheizungen Engineered air DJ Series herunter. Installation, Operation and Maintenance Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 20
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
A
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
FOR
PACK SERIES
UNIT MODEL NO. ______________________________
UNIT SERIAL NO. ______________________________
SERVICED BY: __________________________________
TEL. NO: ______________________________________
SALES OFFICES ACROSS CANADA AND USA
RETAIN INSTRUCTIONS WITH UNIT AND MAINTAIN IN A LEGIBLE CONDITION
PLEASE GIVE MODEL NO. & SERIAL NO. WHEN CONTACTING
FACTORY FOR INFORMATION AND/OR PARTS
FORM #PACK-8.99
CANADIAN
HEAD OFFICE
AND FACTORY
1401-HASTINGS CRES. S.E.
CALGARY, ALBERTA
T2G-4C8
CANADIAN
EASTERN
FACTORY
1175-TWINNEY DRIVE
NEWMARKET, ONTARIO
L3Y-5V7
INDOOR AND OUTDOOR MODELS
INDIRECT GAS FIRED HEATING UNITS
L
I
S
T
E
D
R
L
I
S
T
E
D
R
C
Seitenansicht 0
1 2 3 4 5 6 ... 19 20

Inhaltsverzeichnis

Seite 1 - PACK SERIES

AINSTALLATION, OPERATIONAND MAINTENANCE MANUALFORPACK SERIESUNIT MODEL NO. ______________________________UNIT SERIAL NO. _____________________________

Seite 2

- 9 -13. Check the amperage draw of each motor. Refer to name plate for full load amps.14. Re-check voltage at unit disconnect switch with unit runni

Seite 3

- 10 -OPERATING SEQUENCE FOR INTERMITTENT PILOT SYSTEM WITH OR WITHOUT 100%LOCKOUT DEVICE - STANDARD OUTDOOR (OPTIONAL INDOOR)1. Set thermostat at low

Seite 4

- 11 -OPERATING FUNCTIONS:The three major heating and/or cooling functions of DJ (E,P) units are as follows:Furnace Operation: Defined as space heatin

Seite 5

- 12 -6. MODULATING DAMPER MOTOR: Modulates the outside air and return air dampers to maintain a constant mixedair temperature or to provide multiple

Seite 6

- 13 -28. POWER VENTER RELAY: Provides a signal to start the power venter on a heat call.29. VENTOR FLOW SWITCH: Interrupts combustion if the power ve

Seite 7

- 14 -MAINTENANCEIn order to provide a maintenance history, we recommend that the owner have a maintenance fileon each unit. The following maintenanc

Seite 8

- 15 -3. Set Screws:Check set screws on blower wheel, blower bearings, blower and motor pulleys for looseness on theshaft. Tighten where required. IT

Seite 9

- 16 -5. Motor Lubrication:Refer to motor manufacturer for lubrication recommendations.Follow the highlighted blower bearing recommendations above for

Seite 10

- 17 -8. FurnaceA. Furnace Inspections and Cleaning:Furnaces should be inspected once every four months during the heating season where theequipment i

Seite 11

- 18 -TROUBLE SHOOTING GUIDEPROBLEM POSSIBLE CAUSE CORRECTIONPilot lit, but furnace willnot fire (match litsystem).1) Thermostat set too low.2) Power

Seite 12

- 1 -INSTALLATION, OPERATIONAND MAINTENANCE MANUALINDEXPAGEINTRODUCTION...

Seite 13

- 19 -TROUBLE SHOOTING GUIDE (cont d)PROBLEM POSSIBLE CAUSE CORRECTIONMotor stops duringfurnace operation.1) Excessive current draw.2) Excessive air F

Seite 14

- 2 -INTRODUCTIONThe Engineered Air PACK units are high quality products designed and manufactured to providemany years of trouble-free service. We r

Seite 15

- 3 -RECEIVING THE UNIT:Engineered Air units are usually pre-wired and assembled where possible. On receipt of unit, checkelectrical characteristics

Seite 16

- 4 -LIFTING UNIT:All Engineered Air units are constructed on a heavy base frame. The frame is extended beyond thelength of the unit and is predrille

Seite 17

- 5 -ASSEMBLING THE UNIT:If the unit is split and shipped in sections, the sections must be field assembled into one piece. Allsections are pre-drill

Seite 18

- 6 -An extension is included with the gravity vent cap with all PACK series 300, 350 and 400units. Dimension H is 12 inches (305mm) for propane gas

Seite 19 - TROUBLE SHOOTING GUIDE

- 7 -B) PROPANE GAS (See Name Plate)Manifold pressure is regulated by the combination valve to 10" W.C. (2.49 kPa). Linepressure upstream of the

Seite 20

- 8 -ELECTRICAL INSTALLATION:All wiring shall be installed with the requirements of the authorities having jurisdiction. DO NOT CUTHOLES IN THE BOTTO

Kommentare zu diesen Handbüchern

Keine Kommentare