A SH / S-TRAC MANUAL
12 of 29 Feb 06
Recommended 24V Field Wiring Size:
Copper conductors only
Maximum Total Length of Run
< 50 Ft < 100 Ft
< 150 Ft
< 200 Ft
< 250 Ft
< 300 Ft
< 350 Ft
< 400 Ft
< 450 Ft
< 500 Ft
Circuit
Load
(Amps)
(1)
(~ 15 m)
(~ 30 m)
(~ 45 m)
(~ 60 m)
(~ 75 m)
(~ 90 m)
(~ 105 m)
(~ 120 m)
(~ 135 m)
(~ 150 m)
1 16 AWG
16 AWG
16 AWG
16 AWG
16 AWG
16 AWG
14 AWG
14 AWG
14 AWG
12 AWG
2 16 AWG
16 AWG
16 AWG
14 AWG
12 AWG
12 AWG
12 AWG
10 AWG
10 AWG
10 AWG
3 16 AWG
16 AWG
14 AWG
12 AWG
12 AWG
10 AWG
10 AWG
10 AWG
4 16 AWG
14 AWG
12 AWG
10 AWG
10 AWG
10 AWG
5 16 AWG
12 AWG
12 AWG
10 AWG
6 16 AWG
12 AWG
10 AWG
10 AWG
7 14 AWG
12 AWG
10 AWG
8 14 AWG
10 AWG
10 AWG
9 14 AWG
10 AWG
10 12 AWG
10 AWG
11 12 AWG
10 AWG
12 12 AWG
10 AWG
13 12 AWG
14 12 AWG
15 12 AWG
Notes:
1) The field wiring load depends on the actual load on a particular control circuit the field wiring is
connected to. Refer to the internal wiring diagram of the unit.
2) The table above is based on a maximum 10% voltage drop on a 24V control circuit. Wire size was
calculated using the following formula:
CM = (25 x I x L ) / V
Where CM is circular mils of conductor for a constant load of I amps, wire length L in feet from the unit
to the field device and back, and voltage drop V.
When connecting to a three phase power supply, check for the correct rotation of all motors and fans. If the
rotation is incorrect, reverse the rotation at the incoming power only. All electrical conduit outlets in the
control panel must be sealed to prevent moist building air from migrating to the control panel.
All penetrations through the unit walls must be caulked and sealed to prevent air and/or water from
entering the unit.